| Mounting | DIN rail or wall |
|---|---|
| I/O Mode | DI or Event Counter |
| Wiring | I/O cable max. 14 AWG |
| Shock | IEC 60068-2-27 |
| Counter Frequency | 250 Hz |
| Operating temperature | Standard Models: -10 to 60°C (14 to 140°F); Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
| Freefall | IEC 60068-2-32 |
| Isolation | 3k VDC or 2k Vrms |
| Mechanical Endurance | 5,000,000 operations |
| EMI | EN 55022; EN 61000-3-2; EN 61000-3-3; FCC Part 15, Subpart B, Class A |
| Wet Contact (DI to COM) | On: 10 to 30 VDC; Off: 0 to 3 VDC |
| Contact Resistance | 100 m ohms (max.) |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, HTTP |
| Time | 808,744 hrs |
| Safety | UL 508 |
| Hazardous Location | UL/cUL Class I Diision 2, ATEX Zone 2 |
| Electrical Endurance | 100,000 operations @ 5 A resistive load |
| Sensor Type | Wet Contact (NPN or PNP), Dry Contact |
| Type | Form A power relay |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| Breakdown Voltage | 500 VAC |
| Pulse Output | 0.3 Hz at rated load |
| Protection | 1.5 kV magnetic isolation |
| Digital Filtering Time Interval | Software Configurable |
| EMS | EN 55024, EN 61000-4-2, EN 61000-4-3; EN 61000-4-4, EN 61000-4-5, EN 61000-4-6; EN 61000-4-8, EN 61000-4-11 |
| Common Type | points per COM |
| Storage temperature | -40 to 85°C |
| Power Consumption | 188 mA @ 24 VDC |
| Contact Current Rating | Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC |
| Relay Outputs | 6 channels |
| Digital Inputs | 6 channels |
| Dry Contact | On: short to GND; Off: open |
| Database | Telcordia (Bellcore) |
| Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
| Vibration | IEC 60068-2-6 |
| Ethernet | 2 switched 10/100 Mbps RJ45 ports |
| Initial Insulation Resistance | 1000 M ohms (min.) @ 500 VDC |
| Altitude | Up to 2,000 m |
| Power Input | 24 VDC nominal, 12 to 36 VDC |
| Relay On/Off Time | 1500 ms (Max.) |
| Package Quantity | 1 |