| Mounting | DIN rail or wall |
|---|---|
| Power Input | 24 VDC nominal, 12 to 36 VDC |
| Sampling Rate | All channels: 12 samples/sec; Per channel: 1.5 samples/sec; Only one channel enabled: 12 samples/sec |
| Accuracy | ±0.1% FSR @ 25°C; ±0.3% FSR @ -40 and 75°C |
| Sensor Type | J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C) |
| Altitude | Up to 2,000 m |
| Hazardous Location | UL/cUL Class I Diision 2, ATEX Zone 2 |
| EMS | EN 55024, EN 61000-4-2, EN 61000-4-3; EN 61000-4-4, EN 61000-4-5, EN 61000-4-6; EN 61000-4-8, EN 61000-4-11 |
| Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
| Wiring | I/O cable max. 14 AWG |
| Shock | IEC 60068-2-27 |
| Operating temperature | Standard Models: -10 to 60°C (14 to 140°F); Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
| Input Impedance | 10M ohms |
| EMI | EN 55022; EN 61000-3-2; EN 61000-3-3; FCC Part 15, Subpart B, Class A |
| Protection | 1.5 kV magnetic isolation |
| Millivolt Type | Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV; Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on) |
| Safety | UL 508 |
| Time | 631,418 hrs |
| Resolution | 16 bits |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, HTTP |
| Thermocouple Inputs | 8 channels |
| Database | Telcordia (Bellcore) |
| Power Consumption | 118 mA @ 24 VDC |
| Ethernet | 2 switched 10/100 Mbps RJ45 ports |
| Vibration | IEC 60068-2-6 |
| Storage temperature | -40 to 85°C |
| Freefall | IEC 60068-2-32 |
| Isolation | 3k VDC or 2k Vrms |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| Package Quantity | 1 |