| Parity | None, Even, Odd (default = None) |
|---|---|
| Counter Frequency | 2.5 kHz |
| EMS | EN 55024, EN 61000-4-2 (ESD) Level 3, EN 61000-4-5 (Surge) Level 2; IEC 61000-4, IEC 61000-6 |
| Interface | RS-485-2w: Data+, Data-, GND (5-contact terminal block for two serial port) |
| Stop Bits | 1, 2 |
| Common Type | COM, 8 points |
| Data Bits | 8 |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| Protocols | Modbus RTU |
| Shock | IEC 60068-2-27 |
| Power Consumption | 154 mA @ 24 VDC |
| Storage temperature | -40 to 85°C |
| Operating temperature | Standard Models: -10 to 75°C (14 to 167°F); Wide Temp. Models: -40 to 85°C (-40 to 185°F) |
| Digital Filtering Time Interval | Software Configurable |
| Digital Inputs | 16 channels |
| High/Low Resistor for RS-485 | 1 kΩ, 150 kΩ |
| Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
| I/O Mode | DI or Event Counter |
| Serial Line Protection | ESD Protection: 15 kV; Surge Protection: 1 kV |
| Dry Contact | On: short to GND; Off: open |
| Freefall | IEC 60068-2-32 |
| Sensor Type | Wet Contact (NPN or PNP), Dry Contact |
| Wiring | I/O cable max. 16 AWG |
| Safety | UL 508 |
| Wet Contact (DI to COM) | On: 10 to 30 VDC; Off: 0 to 3 VDC |
| Vibration | IEC 60068-2-6 |
| Baudrate | 1200 to 921.6 kbps (default = 9600) |
| Isolation | 3k VDC or 2k Vrms |
| EMI | EN 55022, EN 61000-3-2, EN 61000-3-3, FCC Part 15 Subpart B Class A |
| Package Quantity | 1 |