Ground Rod Clamp, Steel Zinc Plated
| Item | Raised Floor Grounding Connector |
|---|---|
| Item - Grounding Connector | Raised Floor Grounding Connector |
| Type | Access Floor |
| Type - Grounding Connector | Mechanical |
| Wire Size - Grounding | 6 AWG Solid to 1/0 AWG Stranded |
| Material | Steel |
| Grounding Wires Connected To | 3/4 in to 7/8 in Round Raised Floor Pedestal |
| Standards | TIA-942 / TIA-607-B |
| Material - Grounding Connector | Zinc Plated Steel |
| Number of Wires - Grounding | 1 |
| Material of Construction | Steel Zinc Plated |
| Description/Special Features | 3/4 to 7/8" Round |
| Conductor Size | 6 Solid to 1/0 Stranded |
| Package Quantity | 1 |
| Grounding Wire Size | 6 AWG SOL to 1/0 AWG STR |
| Overall Width | 3-3/8 in |
| Overall Length | 4-1/4 in |
| For Maximum Ground Conductor Wire Size | 1/0 AWG STR |
| For Minimum Ground Conductor Wire Size | 6 AWG SOL |
| Overall Height | 3-3/16 in |
| Torque | 150 in-lb, 385 in-lb |
| Accessory Type | Ground Clamp |