Item - Relay | Phase Monitor Relay |
---|---|
Coil Volts | 250VAC/DC |
AC Contact Rating - Relay | 5A @ 250V |
DC Contact Rating - Relay | 7 A @ 30 V |
Contact Form - Relay | SPDT |
Mounting - Relay | Plug In |
Item | Relay |
Body Width - Relay | 3.07 in |
Body Depth - Relay | 3.78 in |
Phase Loss Sensitivity | No |
Body Height - Relay | 1.1 in |
Base Type - Plug In Relay | Octal |
Restart | Auto |
Input or Control Voltage | 183 to 528 V AC |
Phase Unbalance | No |
Over Voltage | No |
Phase Reversal | No |
Under Voltage | No |
Standards | C-Tick, CSA Certified, EN/IEC 60255-1, EN/IEC 61000-6-4, EU RoHS, GL, GOST, Reach Regulation, UL Listed |
Contact Form | SPDT |
Response Time | < 200 ms (in the event of a fault) |
Maximum Switching Capacity | 1,250 VA |
IP Rating | IP30 |
Number of Pins | 6 |
Input Voltage | 183 to 528V AC |
Flat Pin Width | Not Applicable |
Frequency | 50/60 Hz |
Monitored Parameters | Phase Failure, Phase Sequence |
Maximum Operating Temperature | 122 deg F |
Overvoltage | No |
Maximum Switching Voltage | 250V AC/DC |
Current Rating | 5 A |
Body Height | 3.54 in |
Base Shape | Octal |
Restart Time Delay | 1.5 sec |
Minimum Switching Current | 10 mA |
Mechanical Operating Durability | 30,000,000 |
Power Consumption | 1,250 VA |
Contact Rating (DC) | 7 A @ 30V |
Mounting Style | DIN Rail |
Overall Depth | 2.84 in |
Maximum Switching Current | 5 A |
Body Depth | 2.84 in |
Body Width | 0.69 in |
Electrical Operating Durability | 100,000 |
Minimum Operating Temperature | -4 deg F |
Weight | 4.64 oz |
Contact Rating (AC) | 5 A @ 250V |
Housing Material | plastic |
Product Or Component Type | control relay |
Repeat Accuracy | 0.5 % input and measurement circuit || 3 % time delay |
Tightening Torque | 0.6-1 N.m IEC 60947-1 |
Nominal Output Current | 5 A |
Run-Up Delay At Power-Up | 650 msec |
Measurement Range | 208...480 V voltage AC |
Product Certifications | UL || GL || C-tick || GOST || CSA |
Measurement Error | < 0.05 %/°C with temperature variation || < 1 % over the whole range with voltage variation |
Width | 17.5 mm |
Ambient Air Temperature For Storage | -40-70°C |
Mounting Support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
Contacts Type And Composition | O, 1 C |
Maximum Measuring Cycle | 150 msec |
Voltage Range | 208...480 V phase to phase |
Relay Type | control |
Ambient Air Temperature For Operation | -20-50°C |
Marking | CE |
Local Signalling | for power ON LED (green) || for relay ON LED (yellow) |
Ip Degree Of Protection | IP20 IEC 60529 terminals) || IP30 IEC 60529 casing) |
Electrical Durability | 100000 cycles |
Operating Rate | <= 360 operations/hour full load |
Power Consumption In Va | 0-22 VA 400 V AC 50 Hz |
Hysteresis | 2-2 % |
Operating Position | any position without derating |
Output Contacts | 1 C/O |
Product Specific Application | for 3-phase supply |
Time Delay Type | without |
Overvoltage Category | III IEC 60664-1 |
Threshold Adjustment Voltage | -2...-17 % in the range 220 V AC || 2...20 % of Un selected || +2...+17 % in the range 480 V AC || -2...-12 % in the range 208 V AC |
Shock Resistance | 15 gn 11 ms IEC 60255-21-1 |
Dielectric Test Voltage | 2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1 |
Relay Name | RM17TT |
Supply Frequency | 50/60 Hz +/- 10 % |
Reset Time | 1500 ms time delay |
Control Circuit Voltage Limits | 12 % + 10 % Un |
Switching Capacity In Va | 1,250 VA |
Supply Voltage Limits | 183-528 V AC |
Measurement Voltage Limits | 183 to 528 V AC |
Relative Humidity | 95-95 % 55-55°C IEC 60068-2-30 |
Adjustment Of Asymmetry Threshold | 5...15 % of Un selected |
Mechanical Durability | 30000000 cycles |
Electromagnetic Compatibility | emission standard for industrial environments EN/IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 || immunity for industrial environments EN/IEC 61000-6-2 |
Connections - Terminals | screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
[Ui] Rated Insulation Voltage | 400 V IEC 60664-1 |
[Uc] Control Circuit Voltage | 208...480 V |
Vibration Resistance | 0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1 |
Phase Failure Sensitivity | 0.7 Un |
Insulation Resistance | > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1 |
Relay Monitored Parameters | phase failure detection || phase sequence |
Control Circuit Frequency | 50...60 Hz +/- 10 % |
Pollution Degree | 3 IEC 60664-1 |
Non-Dissipating Shock Wave | 4 kV IEC 60255-5 || 4 kV IEC 60664-1 || 4 kV IEC 61000-4-5 |
Utilisation Category | AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 |
Package Quantity | 1 |