| Item | Manstarter Undervoltage Trip 575Vac Iec |
|---|---|
| Coil Volts | 200 to 220V AC |
| Features | Mercury Free |
| Hz | 50/60 Hz |
| Depth | 66 mm |
| Width | 18 mm |
| Height | 89 mm |
| Weight | 0.105 kg |
| Control Circuit Voltage | 200 V AC 50 Hz; 200 to 220 V AC 60 Hz |
| Color | Dark Gray |
| Control Circuit Voltage Limits | 0.85 to 1.1 Un |
| Tightening Torque | Less than 1.4 N.m screw clamp terminals |
| Mechanical Durability | 10000 cycles with GV3P and GV3L; 30000 cycles with GV2ME and GV2P |
| Product Or Component Type | Undervoltage release |
| Hold-In Power Consumption in VA | 3.5 VA AC |
| Inrush Power in W | 8 W |
| Range Compatibility | TeSys GV2ME; TeSys GV2LE; TeSys GV2L; TeSys GV2P; TeSys GV3L; TeSys GV3P; TeSys Deca |
| Operating Time | 10 to 15 ms IEC 60947-1 |
| On-Load Factor | 1 |
| Threshold Tripping Voltage | 0.7 to 0.35 Un |
| Hold-In Power Consumption in W | 1.1 W |
| Connections - Terminals | screw clamp terminals 1 0.00 to 0.00 in² (1 to 2.5 mm²)solid; screw clamp terminals 2 0.00 to 0.00 in² (1 to 2.5 mm²)solid; screw clamp terminals 1 0.00 to 0.00 in² (0.75 to 2.5 mm²)flexible without cable end; screw clamp terminals 2 0.00 to 0.00 in² (0.75 to 2.5 mm²)flexible without cable end; screw clamp terminals 1 0.00 to 0.00 in² (0.75 to 1.5 mm²)flexible with cable end; screw clamp terminals 2 0.00 to 0.00 in² (0.75 to 1.5 mm²)flexible with cable end |
| Rated Insulation Voltage | 690 V AC IEC 60947-1; 600 V AC UL 60947-4-1; 600 V AC CSA C22.2 No 60947-4-1 |
| Inrush Power in VA | 12 VA AC |
| Package Quantity | 1 |