Arrancador y protector manual TeSys Deca, protector de circuito térmico magnético, manija giratoria, 6 a 10 A, sujeción por tornillo.
| Depth |
97 mm |
| Height |
89 mm |
| Width |
45 mm |
| Item |
MANUAL STARTER / PROTECTOR 6-10 A |
| Standards |
EN/IEC 60947-2, EN/IEC 60947-4-1 |
| Poles Description |
3P |
| Operating Altitude |
6,561.68 ft |
| Power Dissipation Per Pole |
2.5 W |
| Fixing Mode |
35 mm symmetrical DIN rail clipped, panel screwed with 2 x M4 screws) |
| Fire Resistance |
960°C IEC 60695-2-11 |
| Tightening Torque |
1.7 N.m screw clamp terminal |
| Product Name |
TeSys GV2, TeSys Deca |
| Trip Unit Technology |
thermal-magnetic |
| Ip Degree of Protection |
IP20 IEC 60529 |
| Range |
TeSys Deca |
| [Uimp] Rated Impulse Withstand Voltage |
6 kV IEC 60947-2 |
| Utilisation Category |
category A IEC 60947-2, AC-3 IEC 60947-4-1, AC-3e IEC 60947-4-1 |
| Electrical Durability |
100000 cycles AC-3 415 V In, 100000 cycles AC-3e 415 V In |
| Rated Duty |
continuous IEC 60947-4-1 |
| Product or Component Type |
motor circuit breaker |
| [Ith] Conventional Free Air Thermal Current |
10 A IEC 60947-4-1 |
| Ambient Air Temperature For Operation |
-20-60°C |
| [Ui] Rated Insulation Voltage |
690 V AC 50/60 Hz IEC 60947-2 |
| Breaking Capacity |
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2, 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2, 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2, 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2, 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
| Color |
Dark Grey |
| Network Frequency |
50/60 Hz IEC 60947-4-1 |
| [Ue] Rated Operational Voltage |
690 V AC 50/60 Hz IEC 60947-2 |
| Ambient Air Temperature For Storage |
-40-80°C |
| Thermal Protection Adjustment Range |
6-10 A IEC 60947-4-1 |
| [Ics] Rated Service Short-Circuit Breaking Capacity |
100 % 230/240 V AC 50/60 Hz IEC 60947-2, 100 % 400/415 V AC 50/60 Hz IEC 60947-2, 100 % 440 V AC 50/60 Hz IEC 60947-2, 100 % 500 V AC 50/60 Hz IEC 60947-2, 100 % 690 V AC 50/60 Hz IEC 60947-2 |
| Mechanical Robustness |
shocks 30 Gn for 11 ms, vibrations 5 Gn, 5...150 Hz |
| Climatic Withstand |
IACS E10 |
| Ik Degree of Protection |
IK04 |
| Magnetic Tripping Current |
138-138 A |
| Line Rated Current |
10 A |
| Device Application |
motor protection |
| Control Type |
rotary handle |
| Motor Power Kw |
3 kW 400/415 V AC 50/60 Hz; 5 kW 500 V AC 50/60 Hz; 5.5 kW 690 V AC 50/60 Hz |
| Device Short Name |
GV2P |
| Mechanical Durability |
100,000 cycle |
| Network Type |
AC |
| Phase Failure Sensitivity |
yes IEC 60947-4-1 |
| Rated Service Short-Circuit Breaking Capacity |
100% 230/240 V AC 50/60 Hz IEC 60947-2; 100% 400/415 V AC 50/60 Hz IEC 60947-2; 100% 440 V AC 50/60 Hz IEC 60947-2; 100% 500 V AC 50/60 Hz IEC 60947-2; 100% 690 V AC 50/60 Hz IEC 60947-2 |
| Suitability For Isolation |
Yes IEC 60947-1 § 7-1-6 |
| Conventional Free Air Thermal Current |
10 A IEC 60947-4-1 |
| Rated Insulation Voltage |
690 V AC 50/60 Hz IEC 60947-2 |
| Rated Operational Voltage |
690 V AC 50/60 Hz IEC 60947-2 |
| Rated Impulse Withstand Voltage |
6 kV IEC 60947-2 |
| Product Certifications |
CCC; UL; CSA; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL; UKCA |
| Package Quantity |
1 |