Arrancador magnético de motor NEMA no reversible, sin gabinete clasificación NEMA , 120V CA, 3 polos, 1NC.
| Item |
NEMA Magnetic Motor Starter |
| Overload Relay Amp Setting |
6 to 18 A |
| Coil Volts |
120V AC |
| Enclosure NEMA Rating |
No Enclosure |
| Auxiliary Contact Form |
1NO |
| HP @ 3 Phase - 240V |
3 HP |
| Starter Type |
NEMA Style |
| Action |
Nonreversing |
| Amps AC |
18 A |
| NEMA Size |
0 |
| Number of Poles |
3 |
| HP @ 3 Phase - 480V |
5 HP |
| Includes |
Solid state overload relay |
| HP @ 3 Phase - 575V |
5 hp |
| Height |
6.9 in |
| Standards |
CSA, UL Listed |
| Width |
4-1/2 in |
| HP @ 3 Phase - 208V |
3 HP |
| Depth |
3-1/2 in |
| Features |
Solid State Overload Relay |
| Hz |
50/60 |
| Thermal Unit Code |
Not Applicable |
| Enclosure Type |
Open |
| Operating Voltage |
600V AC |
| Horsepower @ Three Phase - 480V AC |
5 HP |
| Reversing Capability |
Non-Reversing |
| Phase |
Three |
| Operator |
None |
| Includes Auxiliary Contacts |
No |
| Horsepower @ Three Phase - 208V AC |
3 HP |
| Overall Width |
3-1/2 in |
| Coil Voltage |
110/120V AC |
| Number of Auxillary Contacts |
0 |
| Includes Pilot Light |
No |
| Operator Function |
Not Applicable |
| Minimum Overload Relay Current Setting |
6 A |
| Horsepower @ Three Phase - 240V AC |
3 HP |
| NEMA Enclosure Rating |
No Enclosure |
| Overall Depth |
4.22 in |
| Terminal Connection Type |
Screw Clamp Terminals |
| Current AC |
18 A |
| Horsepower @ Three Phase - 600V AC |
5 HP |
| Frequency |
50/60 Hz |
| Maximum Voltage Rating |
600 V AC |
| Trip Class |
10/20 |
| Overload Protection Type |
Electronic |
| Overall Height |
6.77 in |
| Maximum Overload Relay Current Setting |
18 A |
| Starter Style |
NEMA |
| Auxiliary Contacts |
Without |
| Control Units |
No control units |
| Horsepower Rating |
3 HP 200 V AC; 3 HP 230 V AC; 5 HP 460 V AC; 5 HP 575 V AC |
| Certifications |
UL Listed, CSA, NEMA |
| Type Of Overload |
Solid state Motor Logic class 10/20 |
| Control Circuit Type |
Separate control circuit |
| Short Circuit Current Rating |
Circuit-breaker 70 A maximum: 100 kA at 480 V AC; Fuse J 60 A maximum: 100 kA at 600 V AC; Fuse T 60 A maximum: 100 kA at 600 V AC; Fuse RK1 60 A maximum: 100 kA at 600 V AC; Fuse RK5 60 A maximum: 100 kA at 600 V AC |
| Pilot Light |
Without pilot light |
| Package Quantity |
1 |