| VA Rating - UPS Systems | 3 kVA |
|---|---|
| Item | Smart UPS |
| UPS Type | Line Interactive |
| Power Rating | 3 kVA |
| Mounting | Tower, Rack |
| Wattage | 3 kW |
| Input Voltage | 120V AC |
| Output Voltage | 100/110/120/125V AC |
| Backup Time (Half/Full Load) | 9 min/3 min |
| Outlet Type | UPS/Surge |
| Medical Grade | No |
| Number of Outlets | 9 |
| Width | 19 in |
| Special Features | Advanced AVR Corrects Brownouts and Overvoltages, Pure Sine Wave Output |
| Transfer Time | 1 msec from DC to AC, 5 msec from AC to DC |
| NEMA Receptacle Configuration | L5-30R, 5-15/20R |
| Display Type | LCD |
| Footnotes | 1,3,4,10,12 |
| Fax/Modem Line Protection | No |
| Standards | CAN/CSA-C22.2 No. 107.3 (Canada), ENERGY STAR Qualified, FCC Part 15 Class a (USA), ICES (Canada), NOM (Mexico), RoHS, UL1778 |
| Input Current | 24 A |
| Phase | Single |
| Cord Length | 10 ft |
| Ports | DB9 Serial, SNMP/Web Slot, USB (HID Enabled) |
| Automatic Volts Regulation | Yes |
| NEMA Plug Configuration | L5-30P |
| Hz | 60 Hz |
| Includes | (4) Post Rack Mount Installation Kits, PowerAlert Software with USB, Serial and EPO Cables |
| Height | 4 in |
| Depth | 19 in |
| Overall Width | 17.2 in |
| Voltage | 120 |
| Input Connection | 10 ft Cord with NEMA L5-30P Plug |
| Battery Type | VRLA |
| Housing Material | Steel |
| Alarm Cancel Operation | Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
| Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
| Relative Humidity | 0 to 95%, non-condensing |
| Battery Recharge Rate (Included Batteries) | Less than 4.5 hours from 10% to 90% |
| Network Management Cards | WEBCARDLX, SNMPWEBCARD, TLNETCARD, RELAYIOCARD |
| Front Panel LCD Display | Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
| Output Voltage Regulation (Battery Mode) | +/- 5% |
| Primary UPS Height (mm) | 87 |
| AC Mode Efficiency Rating (100% Load) | 0.98 |
| Load Management Receptacles | Two switchable single-outlet load banks |
| Individually Controllable Load Banks | Yes |
| Output kW Capacity (kW) | 2.25 |
| UPS Input Cord Length (ft.) | 10 |
| Expandable Battery Runtime | Extended runtime supported via optional external battery packs |
| Voltage Regulation Description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145 |
| Internal UPS Replacement Battery Cartridge | RBC94-2U |
| Installation Form Factors Supported with Optional Accessories | 2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2-9USTAND ); Wallmount ( 2POSTRMKITWM ) |
| Low Voltage Transfer to Battery Power (Setpoint) | 83 |
| Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
| High Availability UPS Features | Hot swappable batteries |
| Battery Access | Front panel battery access door |
| PowerAlert Software | For local monitoring via the UPSâ„¢s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert |
| UPS Certifications | Meets FCC Part 15 Category A (EMI); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA) |
| Included Mounting Accessory Description | Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm) |
| Communications Interface | USB (HID enabled); DB9 Serial; Slot for SNMP/Web interface |
| Rack Height | 2 U |
| Overvoltage Correction | Input voltages between 127 and 145 are reduced by 12% |
| UPS Certification Details | SAFETY STANDARD (U.S.) - UL1778:2014 (5th Ed) R10.17; SAFETY STANDARD (CANADA) - CAN/CSA-C22.2 No. 107.3-14 (3rd Ed) + GI1 / FCC/ICES COMPLIANT - CLASS A |
| Recommended Electrical Service | 30A 120V |
| UPS Power Module Dimensions (hwd, in.) | 3.43 x 17.32 x 19.46 |
| Installation Form Factors Supported with Included Accessories | 4 post 19 inch rackmount |
| Nominal Output Voltage(s) Supported | 110 V, 115 V, 120 V |
| Primary UPS Depth (mm) | 494 |
| AC Mode BTU / Hr. (Full Load) | 189 |
| Network UPS Tools Compatibility | NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite |
| Output Voltage Regulation (Line Mode) | +6%, -14% |
| Power Factor | 0.75 |
| External Battery Pack Compatibility | BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible) |
| Cooling Method | Fan |
| Audible Noise | 45 dBA maximum, front side 1m |
| Nominal Input Voltage(s) Supported | 120 V AC |
| Primary Form Factor | Rackmount |
| Output AC Waveform (Battery Mode) | Pure Sine wave |
| Output kVA Capacity (kVA) | 3 |
| UPS AC Suppression Response Time | Instantaneous |
| Network Monitoring Port Description | Supports detailed monitoring of UPS and site power conditions |
| Full Load Runtime (min.) | 3 min 30 sec |
| Audible Alarm | Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
| Severe Undervoltage Correction | Input voltages between 83 and 95 are boosted by 24% |
| Output Capacity Details | Output is reduced to 1600 watts maximum when used with external battery packs |
| Half Load Runtime (min.) | 10 min |
| WatchDog Compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
| Expandable Runtime | Yes |
| Battery Mode BTU / Hr. (Full Load) | 1,356 |
| DC System Voltage (VDC) | 48 |
| High Voltage Transfer to Battery Power (Setpoint) | 145 |
| Communications Cable | USB and DB9 cabling included |
| EMI / RFI AC Noise Suppression | Yes |
| Rated input current (Maximum Load) | 24 A |
| Grounding Lug | Includes |
| Battery Replacement Description | Hot-swappable, user replaceable batteries |
| Input Phase | Single-Phase |
| Undervoltage Correction | Input voltages between 108 and 96 are boosted by 12% |
| Output Circuit Breakers | Two 20A output breakers protect 4 5-15/20R outlets each |
| Minimum Required Rack Depth without External Battery Pack (in.) | 24.46 |
| UPS AC Suppression Joule Rating | 570 |
| Output Volt Amp Capacity (VA) | 3,000 |
| Output Watt Capacity (Watts) | 2,250 |
| Minimum Required Rack Depth with External Battery Pack (in.) | 26.46 |
| Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported |
| Switches | 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
| USB | Yes |
| Software Included | PowerAlert Software |
| Protection Type | Under Voltage |
| Maximum Operating Temperature | 104°F |
| Emergency Power OFF | Yes |
| Alarm | Low Battery, Overload, On Battery |
| Waveform Type | Sine Wave |
| Status Indicators | 5 Front Panel Leds:Green Power Led, Green Voltage Correction Led, 3 Color Battery Charge Led, 3 Color Output Load Led, Red Battery Warning Led |
| Load Capacity | 3000 VA/3000 W |
| Network Management | SNMP Manageable |
| Hot Swappable | Yes |
| Typical Battery Recharge Time | 4 hr 30 min |
| Package Contents | SMART3000RM2U UPS System, Poweralert Software With Usb, Serial & Epo Cabling, 4 x Post Rackmount Installation Kit, Instruction Manual |
| Recycled | No |
| Storage Elevation (ft.) | 0-32,808 |
| Nominal Input Voltage Description | 80V-151V; adjustable to 70-153V |
| LED Indicators | UPS Mode On (Solid Green); Battery Mode (Solid Orange)/ Battery Below Warning Level (Flashing Orange); Fault/Alarm (Solid Red). |
| Output Capacity (VA) | 3,000 |
| Product Certifications | CAN/CSA-C22.2 No. 107.3 (Canada); ICES (Canada); NOM (Mexico); UL 1778 |
| UPS Applications | High-End Desktop/Small Network; Large Network |
| Product Compliance | ENERGY STAR Qualified; FCC Part 15 Class A (USA) |
| Minimum Required Rack Depth (inches) | 27 |
| Package Includes | 3000VA 3000W 120V Line-Interactive UPS;USB cable;DB9 cable;Rack-mounting hardware;Tower support stands;Safety instructions;Advanced User Guide |
| Output Capacity (Watts) | 3,000 |
| Grounding Details | Rear panel grounding lug |
| Unit Dimensions (hwd / in.) | 3.4 x 17.2 x 23.7 |
| Operating Elevation (ft.) | 0-10,000 |
| Manufacturer Warranty | 2 yr, 3 yr (Registration) |
| Automatic Voltage Regulation | Includes Automatic Voltage Regulation |
| Power Rating - Real | 3 kW |
| Operating Temperature - Minimum | 32 deg F |
| Input Current - Maximum | 24 A |
| Power Cord Length | 10 ft |
| Audible Alarm Conditions | Low Battery, Overload, Power Outage |
| Data Line Protection | Includes Data Line Surge Protection |
| Battery Recharge Time | 5 hr |
| Output Ports Included | DB9 Serial, SNMP, USB |
| Operating Temperature - Maximum | 104 deg F |
| Surge Suppression Rating | 380 J |
| Includes Battery | Battery Included |
| External Battery Compatible | Not External Battery Pack Compatible |
| Package Quantity | 1 |